Managing Disk Drives and Enclosures
To blink a disk drive LED:
1 From the System Menu, select Utilities Menu and press Enter.
The Utilities menu appears.
2 Select Drive Utilities Menu and press Enter.
The Drive Utilities menu appears.
3 Select Blink Drive LED and press Enter.
The Select Drive(s) menu appears.
4 Select the disk drive you want and press Enter.
That disk drive’s LED begins to blink.
5 Press Esc to stop blinking the LED.
Taking Down a Disk Drive
Caution: This function is only for testing arrays and should
not be used in normal operation.
The Down Drive Function sets the status of a disk drive in a fault-
tolerant array to Down. This forces the controller to remove it from
the array and marks the array as critical. When a disk drive is
down and the array is critical, you can’t take down any additional
disk drives in that array.
To bring the disk drive up again, you must use Rescan. See
Rescanning All Channels on page 5-21. After you rescan, you must
clear the metadata from the disk drive before you can use it in an
array or as a spare. See Clearing Metadata from a Disk Drive on
page 6-3.
!