DPU Switch Settings and Button Controls
new CE code image and store it into flash memory. See
Chapter 5, "Installing CP Firmware Flash Via Network
Download."
F X Normal operating mode. Will use the database stored in
flash if available.
DPU Key Switch
Use the DPU key switch, located at the bottom part of the DPU chassis, to
select one of four operating modes. The DPU can operate with the key in
place or removed; you can remove the key from the switch regardless of key
position.
The Key Switch requires a key to change the operating mode of the DPU.
The following is a summary of the switch operation.
Position Description
Run Normal execution of control logic. The DPU will accept
database downloads.
Lock Normal execution of control logic. The DPU will not
accept full database downloads in this mode.
Off-line Will scan inputs but not change any outputs (the outputs
freeze at their last value when entering Off-line mode).
The DPU will accept database downloads.
Between the Valid
Positions
After short time delay will place the DPU in the Offline
mode. If the reset button is pressed in this mode a “hard”
reset will be generated to the DPU. This will cause the
DPU to reset without saving the current database. That
means that when the DPU finishes booting it will not have
a database and one must be downloaded to it.
Using the Reset Button
Pressing this button will cause the DPU to stop controlling and go through a
reset cycle. This should not be done casually as it can cause a severe
disruption to your process.
If the Reset button is pressed while the key switch is in the Run, Lock, or
Off-line position, a soft reset will be generated. In a soft reset, the DPU saves
its database into non-volatile (flash) memory before resetting. After the reset,
the DPU will reload the database that it saved.
If the Reset button is pressed while the key switch in set to a position in-
between the valid detent positions (i.e., not in Run, Lock or Off-Line
position), a hard reset will be generated. In a hard reset, the database is not
saved before the DPU resets. After the reset, the DPU will not have a
database and one will have to be downloaded to it.
If you turn the key switch to an “in-between” position to perform a hard
reset, remember to turn it back to the desired position after pressing the reset
button.
Metso Automation MAX Controls Inc. 278590
3-3