Chapter 6
Redundant DPU Operation
Overview
In a redundant configuration, two DPUs are connected to form a backup pair.
One DPU is designated as the primary unit and the other DPU the secondary
unit. The IP address of the secondary DPU is always one number greater than
the address of the primary DPU. The Primary is always the even address
while the Secondary is the odd address.
The installation, preparation, and adjustment procedures included in this
publication apply to both DPUs in a redundant configuration. This chapter
provides information on switches and cabling in a redundant configuration.
Automatic Failover / Manual Takeover
Process control can be transferred between DPUs in a backup pair either
automatically (Failover), or by manual command (Takeover). Automatic
Failover can occur from either the primary DPU to the secondary DPU or
from the secondary to primary based on the health of each DPU. Manual
failover does not depend upon the relative health of the DPUs.
Automatic Failover
Process control is automatically transferred from the active DPU to the
inactive DPU when the active DPU experiences a severe diagnostic alarm or
when communication between active and inactive DPU is lost. However, if
the inactive DPU is itself experiencing a severe diagnostic alarm, it will
refuse control, unless the active DPU loses power or is reset.
In general, each DPU calculates a value for its “health”. The health value
depends on a number of things including network errors, I/O errors and
backup link errors. An inactive DPU will not automatically take over control
from an active DPU if the health of the inactive is less than the health of the
active DPU.
Manual Takeover
To manually command either DPU to assume control, press the Takeover
button on the front panel of the inactive DPU. Manual takeover will occur
only if the inactive DPU is “hot” (has a good copy of the active DPU’s
Metso Automation 278590