Installing Windows CE and maxDNA Software into DPU Flash Memory
Note: Under special circumstances the check box, labeled No IOM
Download, can be checked to skip the download of the IOM.
Note: the software will always download from the c:\mcs\setup folder, so if
an alternate file is to be downloaded, the file
must be located in c:\mcs\setup.
WARNING - New DPUs are normally shipped with the latest production
versions of firmware. However, you may be running an older version at your
plant. It is your responsibility to verify that the correct version of firmware is
installed in each DPU before putting the DPU into service.
The versions of the CP and IOM firmware may be seen on the maxVUE
DPU4E Details display.
7. Click the Go button to start flashing.
Several retries are automatically included to insure proper programming.
However, if the Download does not start then reset the DPU and start over
making sure IP address and Mode switch settings are correct.
When completed the three top LEDs and the IOM LEDs will flash yellow.
8. After the Verify operation has completed set the Mode Switch back to “F”
and reset the DPU.
9. After the DPU boots, verify that its date and time are correct.
Installing CP Firmware Flash via Serial Download
Should there be a problem with the maxNET network connection, you may
download a CE image from a PC to a DPU using the DPU serial port 1. This
serial flash operation may take between 30 to 60 minutes to complete.
Use the DOS program serflsh.exe to download a CE image (nk.bin) through
the serial port. This program, which will download at the maximum baud rate
of 115Kbps, cannot be run successfully at this baud rate in a DOS window. It
must be run in true DOS boot mode.
To perform a serial download, you will need the following parts:
• LAP Link Cable for connection between PC and DPU Chassis Port
(Metso Automation part # 046853)
• 9 pin male to male gender changer
To serially download to a DPU:
1. Connect the serial port of the PC to the Serial 1 port of the DPU using a
Lap Link cable (Metso Automation part # 046853) or equivalent null
modem cable.
Metso Automation MAX Controls Inc. • 278590 •